Bryant 310AAV Furnace Bryant 310AAV Furnace
Find Your Bryant 310AAV Furnace Diagnostic and error LED Code here.
Bryant 310AAV furnace provides a LED on its integrated furnace control for quick diagnostic. Here is its diagnostic code error codes:
Bryant 310AAV
Induced-Combustion
4-Way Multipoise Furnace
The 310AAV/JAV 4-Way Multipoise Gas Furnace was designed by Bryant
dealers for Bryant dealers. Applications are easy with 4-way multipoise
design, through-the-furnace downflow venting, 13 different venting options,
and a door designed for easy service access. An inner blower door is
provided for tighter sealing in sensitive applications. The 310AAV/JAV
furnace is approved for use with natural or propane gas, and the 310JAV is
also approved for use in Low NOx Air Quality Management Districts.
STANDARD FEATURES
• Noise elimination combustion system
• Microprocessor based control center
Adjustable heating air temperature rise
LED diagnostics and self test feature
• Patented blocked vent safeguard to ensure proper furnace venting
• All models are Chimney Friendly when used with accessory vent kit
• Four-position furnace: upflow, horizontal right, horizontal left,
downflow
Thirteen different vent options
• Heat pump compatible
• Hot surface ignition (HSI)
• Residential installations eligible for consumer financing through the Comfort
Credit Program
• Twinning in Upflow, Downflow and Horizontal
LIMITED WARRANTY
• 20-year warranty on “Super S™” heat exchanger
• 5-year parts warranty on all other components
Replacement Part
Code
Coding
Eliminate credit card debt
If status code recall is needed, briefly remove then reconnect one main limit wire to display stored status code. On RED LED boards do not remove power or blower door before initiating status code recall. After
status code recall is completed component test will occur.
LED CODE STATUS
CONTINUOUS OFF – Check for 115VAC at L1 and L2, and 24VAC at SEC-1 and SEC-2.
CONTINUOUS ON – Control has 24VAC power.
RAPID FLASHING – Line voltage (115VAC) polarity reversed. If twinned, refer to twinning kit instructions.
EACH OF THE FOLLOWING STATUS CODES IS A TWO DIGIT NUMBER WITH THE FIRST DIGIT DETERMINED BY THE NUMBER OF SHORT FLASHES AND THE SECOND DIGIT BY THE NUMBER OF LONG FLASHES.
11 NO PREVIOUS CODE – Stored status code is erased automatically after 72 hours. On
RED LED boards stored status codes can also be erased when power
(115 VAC or 24 VAC) to control is interrupted.
12 BLOWER ON AFTER POWER UP (115 VAC or 24 VAC) -Blower runs for 90 seconds,
if unit is powered up during a call for heat (R-W closed) or R-W opens during blower
on-delay.
13 LIMIT CIRCUIT LOCKOUT – Lockout occurs if the limit, draft safeguard, flame rollout, or
blocked vent switch (if used) is open longer than 3 minutes or 10 successive limit trips
occurred during high-heat. – Control will auto reset after three hours. – Refer to #33.
14 IGNITION LOCKOUT – Control will auto-reset after three hours. Refer to #34.
21 GAS HEATING LOCKOUT – Control will NOT auto reset.
Check for: – Mis-wired gas valve -Defective control (valve relay)
22 ABNORMAL FLAME-PROVING SIGNAL – Flame is proved while gas valve is deenergized.
Inducer will run until fault is cleared. Check for: – Leaky gas valve
- Stuck-open gas valve
23 PRESSURE SWITCH DID NOT OPEN Check for:
- Obstructed pressure tubing. – Pressure switch stuck closed.
24 SECONDARY VOLTAGE FUSE IS OPEN Check for:
- Short circuit in secondary voltage (24VAC) wiring.
If you feel that you have benefited from this site, and would like to show your appreciation, you can throw a buck or two in the Tip Jar – Thank you!
31 PRESSURE SWITCH DID NOT CLOSE OR REOPENED – If open longer than five minutes,
inducer shuts off for 15 minutes before retry. Check for: – Excessive wind
- Proper vent sizing – Defective inducer motor
- Low inducer voltage (115VAC) – Defective pressure switch
- Inadequate combustion air supply – Disconnected or obstructed pressure tubing
- Low inlet gas pressure (if LGPS used) – Restricted vent
If it opens during blower on-delay period, blower will come on for the selected blower
off-delay.
33 LIMIT CIRCUIT FAULT – Indicates the limit, draft safeguard, flame rollout, or blocked vent
switch (if used) is open or the furnace is operating in high-heat only mode due to 2
successive low heat limit trips. Blower will run for 4 minutes or until open switch remakes
whichever is longer. If open longer than 3 minutes, code changes to lockout #13.
If open less than 3 minutes status code #33 continues to flash until blower shuts off.
Flame rollout switch and BVSS require manual reset. Check for: – Restricted vent
- Proper vent sizing – Loose blower wheel. – Excessive wind
- Dirty filter or restricted duct system.
- Defective blower motor or capacitor. – Defective switch or connections.
- Inadequate combustion air supply (Flame Roll-out Switch open).
34 IGNITION PROVING FAILURE – Control will try three more times before lockout #14
occurs. If flame signal lost during blower on-delay period, blower will come on for the
selected blower off-delay. Check for: – Flame sensor must not be grounded
- Oxide buildup on flame sensor (clean with fine steel wool).
- Proper flame sense microamps (.5 microamps D.C. min., 4.0 – 6.0 nominal).
- Gas valve defective or gas valve turned off – Manual valve shut-off
- Defective Hot Surface Ignitor – Control ground continuity
- Low inlet gas pressure – Inadequate flame carryover or rough ignition
- Green/Yellow wire MUST be connected to furnace sheet metal
45 CONTROL CIRCUITRY LOCKOUT Auto-reset after one hour lockout due to;
- Gas valve relay stuck open – Flame sense circuit failure – Software check error
Reset power to clear lockout. Replace control if status code repeats.